The safe operation of the Liquid Oxygen Storage Tank relies on the accurate judgment of Liquid Level. The selection of the Liquid Level measurement device, the correspondence between the Liquid Level scale and the volume, and the standardization of the filling operation all directly impact the stability and safety of the system.
The selection of the Liquid Level measurement device must meet the characteristics of the Liquid Oxygen medium, Design Pressure, and temperature requirements, and must have explosion-proof and anti-leakage functions. According to GB/T 18442.6-2019 standard, the Liquid Level measurement device should accurately indicate the Liquid Level with an accuracy grade of no lower than 2.5. For the flammable and explosive Liquid Oxygen medium, an explosion-proof Level Gauge must be used, and a leakage protection device must be installed. In addition, the installation location of the Level Gauge should be convenient for observation and operation, and a clear mark must be made at the highest safe Liquid Level.
The Level Gauge must be equipped with a Liquid Oxygen medium density range and a Liquid Level scale and volume reference table to ensure measurement accuracy. According to GB/T 18442.6-2019 standard, this reference table should clearly indicate the corresponding Storage Tank volume for different Liquid Level heights to facilitate operators in real-time monitoring of the Liquid Oxygen volume inside the tank. For example, in a Liquid Oxygen Storage Tank determined according to the design conditions, the Level Gauge scale must be precisely matched to the actual volume. Considering the variation in Liquid Oxygen density with temperature, the reference table must cover these changes.
The filling process must refer to equipment parameters and operating procedures to ensure that pressure and Liquid Level are within the safe range. During the first filling, the moisture and dust in the filling pipeline should be purged first. Open the Venting, fill, balance valve, and Level Gauge upper and lower valves, and fill slowly from the top. When the Venting valve stabilizes the exhaust, the filling speed can be increased and the balance valve can be closed. Wait for the Level Gauge to display before opening the lower filling valve. When the fill valve flows out liquid, it indicates that the Liquid Level is full. At this point, close all filling valves and the Venting valve. After Filling is completed, the pressure inside the tank should be maintained above 0.5 MPa, and the Liquid Level should be confirmed by the Level Gauge in the end. During Pipeline maintenance or peak load periods, filling operation must pay special attention to pressure control. For example, the Tanker Truck must be pressurized to 0.6 MPa before opening the filling valve. During the Filling process, the Pressure Gauge must be monitored throughout. If the pressure is too high, pressure relief should be performed in time. In addition, the maximum allowable Filling volume of the Tank Shell should be based on the weighing scale, and the Liquid Level measurement device is only an auxiliary measurement means.
When selecting the Liquid Level measurement device, it is necessary to consider the geometric volume of the Liquid Oxygen Storage Tank (e.g., 1m³ to 200m³), Working Pressure (0.8MPa to 3.5MPa), and Design Temperature (-196°C). During filling operations, strict adherence to equipment parameters and operating procedures is required to ensure pressure and Liquid Level remain within safe limits. Through standardized operation and accurate measurement, safety risks in the Liquid Oxygen system caused by Liquid Level anomalies can be effectively prevented.
Liquid Oxygen Storage Tank · Medical central oxygen supply