National standard for single tank volume of Medical Liquid Oxygen Storage Tank shall be formulated by combining actual oxygen demand with requirements for fire separation distances in GB 50030-2013 "Design Code for Oxygen Station" Table 3.0.4. This standard directly relates to the stable operation of hospital central oxygen supply system and patient safety.
Volume of Medical Liquid Oxygen Storage Tank shall be determined based on required usage or storage time, while considering whether the liquid supply unit can replenish in time. This judgment is derived from actual operating conditions, for example in Medical center oxygen supply systems, 5-15m³ Medical Liquid Oxygen Storage Tank is often used as the main gas source, accompanied by Vaporizer, Pressure Regulator, Pressure Stabilization tank, to ensure 24-hour stable oxygen supply for the entire hospital. Selecting appropriate volume shall ensure that necessary oxygen supply can still be maintained when the liquid supply unit cannot replenish in time.
Medical Liquid Oxygen Storage Tank must meet strict safety requirements, including Lightning Protection, Static Electricity Protection and fire separation distance regulations. Lightning Protection grounding resistance shall not exceed 30Ω, Static Electricity Protection grounding resistance shall not exceed 10Ω. Flanges and threaded connections on oxygen equipment, Pipeline, Valve must be cross-connected with metal wires, with cross-connection resistance less than 0.03Ω. Fire separation distances shall be determined according to GB 50030-2013 "Design Code for Oxygen Station" Table 3.0.4, for example distances from open flames or sparking locations shall be categorized based on Storage Tank volume: ≤1000m³ Storage Tank takes 25m, 1000~50000m³ Storage Tank takes 30m, >50000m³ Storage Tank takes 35m.
Installation distance of Medical Liquid Oxygen Storage Tank shall comply with national standards to ensure safe distance from surrounding facilities. Distance between plant roads and Storage Tank shall be taken from "Plant roads (side)" column in GB 50030-2013 Table 3.0.4, with main road distance of 10m (Storage Tank≤1000m³) and 10m (1000~50000m³), secondary road distance of 5m. A fence or railing should be installed around Storage Tank with fire prohibition signs, with fence height not less than 2.5m. If buildings are outside the fence, distance shall not be less than 5m.
Correctly selecting volume of Medical Liquid Oxygen Storage Tank requires comprehensive consideration of oxygen demand, GB 50030-2013 "Design Code for Oxygen Station" and installation conditions. It is recommended to select appropriate volume based on actual operating conditions and ensure compliance with GB 50030-2013 to guarantee safe and stable operation of oxygen supply system. For more detailed information about Medical Liquid Oxygen Storage Tank, refer to Liquid Oxygen Storage Tank or consult professionals. When installing, first verify whether fire separation distance between Storage Tank and surrounding buildings complies with GB 50030-2013 Table 3.0.4.