Troubleshooting and Handling Safety Valve Malfunctions for Liquid Oxygen Storage Tanks

Industry News · 2026-11-17 01:01:42

Liquid Oxygen Storage Tank Safety Valve Troubleshooting and Handling

The safety valve of a liquid oxygen storage tank should be calibrated and periodically verified in accordance with GB/T 18442.6-2019 standards if it fails to operate. This valve is a critical safety accessory for cryogenic containers and is typically preceded by a three-way valve to prevent accidental operation. All liquid-phase pipelines are equipped with dual valves to further enhance system safety. The proper functioning of the safety valve is essential for enabling automatic pressure relief in case of overpressure conditions.

Requirements for Safety Valve Maintenance and Verification

Safety valves require regular verification in compliance with special equipment regulations and metrological procedures. For example, safety valves for hospital liquid oxygen storage tanks must be verified at least once per year, while pressure gauges are typically calibrated every six months according to metrological standards. Vacuum insulated storage tanks should undergo vacuum level testing at least once per year. If the vacuum level declines, it is necessary to promptly contact the manufacturer for vacuum re-pumping. Annual and periodic inspections are fundamental to ensuring long-term reliable operation of safety valves.

Methods for Troubleshooting Safety Valve Malfunctions

If condensation or frost appears on the valve housing, it may indicate a decline in vacuum level, necessitating a comprehensive inspection. If the vacuum level drops below 13.3Pa, re-pumping may be considered. Maintaining vacuum levels is crucial for preserving insulation performance.

Common causes of safety valve malfunctions include valve jamming, spring failure, excessive back pressure, and purity issues with the medium. During on-site troubleshooting, first observe whether condensation or frost is present on the valve housing, then check if the pressure gauge reading is normal. If the pressure gauge displays anomalies, first close the valve and then relieve pressure to rule out potential misoperations. After completing the handling process, the operating pressure of the safety valve must be re-measured to ensure it meets design requirements.

Inspect whether the medium is leaking from the safety valve's discharge port and verify if the pressure gauge reading is normal.

Related articles
The principle of vacuum insulation for low-temperature storage tanks, and how to control the evaporation loss of liquid oxygen, liquid nitrogen, and liquid argon storage tanks Liquid Carbon Dioxide Storage Tank Pressure Analysis How to Select a Vaporizer for Low-Temperature Storage Tanks? Analysis of Complete Gas Supply Solutions for Liquid Oxygen, Liquid Nitrogen, and Liquid Argon Storage Tanks